Busway Short-Circuit Performance Explained
Icw, Ipk & Fault Level Guide
When selecting a busway system, rated current alone is not enough. The busway must also withstand the thermal and mechanical stresses created during short-circuit faults. For this reason, engineers should review short-time withstand current (Icw), peak withstand current (Ipk), system fault level, protection coordination and fault duration before final selection.
Icw represents the RMS short-circuit current that the busway can withstand for a specified period, such as 1 second. It mainly relates to thermal stress in conductors and joints. Ipk, by contrast, represents the maximum instantaneous current peak and is mainly associated with mechanical stress and electromagnetic forces inside the busway.
The required short-circuit performance depends on the system fault level at the busway location. Fault current is usually higher close to transformers and main LV switchgear and may decrease or change further downstream depending on system impedance and configuration.
Busway short-circuit capability must also be coordinated with protective devices such as ACBs, MCCBs and fuses. The objective is to ensure that the busway can withstand the fault until the protection device clears it.
For technical review, customers should provide the SLD, rated current, transformer rating and impedance, prospective fault current, required fault duration, protection device information, busway location and project specification.